Sign In | Join Free | My himfr.com
Home > Transformer Testing Equipment >

JF-2004 Easy Use Portable Transformer Partial Discharge Detector

Delta Technology (Chongqing) Co., Ltd.
Trust Seal
Verified Supplier
Credit Check
Supplier Assessment
Contact Now
    Buy cheap JF-2004 Easy Use Portable Transformer Partial Discharge Detector from wholesalers
     
    Buy cheap JF-2004 Easy Use Portable Transformer Partial Discharge Detector from wholesalers
    • Buy cheap JF-2004 Easy Use Portable Transformer Partial Discharge Detector from wholesalers
    • Buy cheap JF-2004 Easy Use Portable Transformer Partial Discharge Detector from wholesalers
    • Buy cheap JF-2004 Easy Use Portable Transformer Partial Discharge Detector from wholesalers
    • Buy cheap JF-2004 Easy Use Portable Transformer Partial Discharge Detector from wholesalers
    • Buy cheap JF-2004 Easy Use Portable Transformer Partial Discharge Detector from wholesalers
    • Buy cheap JF-2004 Easy Use Portable Transformer Partial Discharge Detector from wholesalers

    JF-2004 Easy Use Portable Transformer Partial Discharge Detector

    Ask Lasest Price
    Brand Name : Delta
    Model Number : JF-2004
    Certification : ISO9001
    Price : USD1.0 / set
    Payment Terms : L/C, D/A, D/P, T/T, Western Union, MoneyGram
    Supply Ability : 100 sets Partial Discharge Detector / month
    Delivery Time : Within 10 days after the order is confirmed
    • Product Details
    • Company Profile

    JF-2004 Easy Use Portable Transformer Partial Discharge Detector

    JF-2004 Easy Use Portable Transformer Partial Discharge DetectorJF-2004 Easy Use Portable Transformer Partial Discharge DetectorJF-2004 Easy Use Portable Transformer Partial Discharge Detector


    Introduction:

    The detector is used for the detection and evaluation of the insulation status of high-voltage switchgear, ring network cabinets, transformers, GIS, overhead lines, cable terminals, cable branch boxes, and other equipment.


    It is widely used in the following fields:

    • Development and distribution enterprises
    • Railway system
    • Petrochemical power supply system
    • Aerospace testing field
    • Automatic testing field

    Partial discharge intensity detection: By measuring the discharge signal within a power frequency period, the intensity of partial discharge is characterized according to the maximum value (dB) in the discharge pulse sequence.

    Partial discharge frequency detection: The device measures the discharge signal within a power frequency period, extracts discharge pulses, and characterizes the frequency of partial discharges according to the number of discharge pulses.


    Main Features:

    1. Configure different sensors to realize partial discharge detection of almost all electrical equipment;
    2. The humanized man-machine interface facilitates data management of different devices, including traceback of historical data change trends, and horizontal and vertical data analysis, and realizes 360 ° comprehensive diagnosis of the device under test;
    3. Built-in ultrasonic sensors and transient ground voltage (hereinafter referred to as TEV) sensors, which can be connected with special sensors such as transformers, GIS, overhead lines, and cables;
    4. Adopt a non-intrusive detection method, no power failure during the test, and maybe no high voltage source is applied, which is more convenient to use than a traditional pulsed partial discharge detector;
    5. The test bandwidth range is 30kHz ~ 2.0GHz, suitable for the detection principle of various frequency bands;

    Parameters:

    TEV measurementUHF measurement
    Measuring range0-60 dBmVdetection frequency300-2000MHz
    Resolution1dBmeasurement range0-60 dBmV
    Accuracy±1dBaccuracy<1dBmV
    Maximum pulse per cycle1400Sensor band300-2000MHz
    Measurement frequency band3~100MHz
    AA measurementAE measurement
    Measuring range-6dBμV - 68dBμVMeasuring range-6dBμV - 68dBμV
    Resolution1dBResolution1dB
    Accuracy±1dBAccuracy±1dB
    Sensor center frequency40 kHzFrequency range20~200 kHz
    HFCT measurement
    Sensor transmission impedance5mV/mA
    Detection frequency1~30MHz
    Sensitivity≤50pC
    Hardware
    ShellABS
    Display4.0 inch RGB LCD screen
    ControllerARM
    Connector

    USB interface (also charger input) 3.5mm stereo headphone jack

    External ultrasonic sensor input wireless wifi Wireless synchronization benchmark

    Earphoneminimum 8 ohm
    SD cardstandard 16G
    Built-in battery3.7V/1Ah lithium battery
    Working timeabout 8 hours
    ChargerAC 90-264V or DC 5V
    Operating temperature-20 ~ 50℃
    Humidity20-85% relative humidity
    Weight0.4KG(host)